Item Name | Circuit Breaker |
Federal Supply Group (FSG) | Electrical and Electronic Equipment Components |
Federal Supply Class (FSC) | 5925 Circuit Breakers |
National Item Identification Number (NIIN) | 00-173-1036 (001731036) |
NCB Code | USA (00) |
Manufacturer | Eaton Corporation, Eca Etablissement Central Des, Sensata Technologies Inc |
Part Number | Manufacturer | Item Name | Cage Code | RFQ |
---|---|---|---|---|
AM633MG6-20 | eaton corporation | circuit breaker | 74193 | RFQ |
72-330-1MG6 | eaton corporation | circuit breaker | 74193 | RFQ |
5925001731036 | eca etablissement central des | circuit breaker | a00am | RFQ |
APL115-2816-1 | sensata technologies inc | circuit breaker | 81541 | RFQ |
MRC | Criteria | Characteristic |
---|---|---|
AAJE | THREAD PITCH DIAMETERS | 0.1177 TO 0.1214 INCHES |
AAQL | BODY STYLE | MULTIPOLE-MULTIPLE ACTUATOR TYPE |
ADAQ | BODY LENGTH | 2.530 INCHES NOMINAL |
ADAT | BODY WIDTH | 2.280 INCHES NOMINAL |
AEBP | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH | 1.950 INCHES NOMINAL |
AEBQ | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH | 0.750 INCHES NOMINAL |
AEBY | DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH | 2.070 INCHES NOMINAL |
AEGJ | SWITCH CONTACT ARRANGEMENT | SINGLE POLE,SINGLE THROW,NORMALLY CLOSED |
AEHA | DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH | 0.750 INCHES NOMINAL |
AJEC | BOSS HEIGHT | 0.150 INCHES NOMINAL |
AJWX | MOUNTING SURFACE TO TERMINAL END DISTANCE | 2.540 INCHES NOMINAL |
AKPX | POLE QUANTITY | 3 |
AXHR | MOUNTING FACILITY TYPE AND QUANTITY | 6 THREADED HOLE |
CMLP | THREAD QUANTITY PER INCH | 32 |
CPLM | MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 20.0 AMPERES AC ALL LOCATIONS |
CPRF | OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 250.0 AC ALL LOCATIONS |
CPRG | MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 1500.0 AC ALL LOCATIONS |
CPRH | CIRCUIT PROTECTION TYPE | OVERCURRENT ALL LOCATIONS |
CPRJ | TRIP RELEASE METHOD | MAGNETIC-HYDRAULIC ALL LOCATIONS |
CPRL | TRIP RELEASE CHARACTERISTIC | TIME DELAY ALL LOCATIONS |
CPRN | ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 150.0 ALL LOCATIONS |
CPRP | ULTIMATE TRIP TIME PER POLE IN SECONDS | 500.000 NOMINAL ALL LOCATIONS |
CPRQ | RESET METHOD | MANUAL |
CPRR | MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
CPRT | MANUAL ACTUATOR TYPE AND QUANTITY | 3 TOGGLE |
CPRW | ACTUATOR FUNCTION | RESET |
CPRX | ACTUATOR POSITION DESIGNATION | AT EACH POLE |
CPRY | EXTERNAL ACTUATOR LINKAGE ARRANGEMENT | ONE,TWO,AND THREE LINKED |
CPRZ | AUXILIARY SWITCH FUNCTION AND QUANTITY | 1 ALARM |
CPSM | INTERNAL TRIP RELEASE CONFIGURATION | SERIES TRIP ALL LOCATIONS |
CQJX | NOMINAL THREAD SIZE | 0.138 INCHES |
CQSM | SWITCH LOCATION AND POSITION DESIGNATION | INTERNAL AT POLE ONE |
CQWN | TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 25.000 MINIMUM AT 200 PCT AND 150.000 MAXIMUM AT 200 PCT ALL LOCATIONS |
CRTK | SWITCH TERMINAL TYPE | THREADED STUD |
CSSX | SWITCH CURRENT RATING AND TYPE IN AMPS | 20.0 AC |
CSWP | SWITCH VOLTAGE RATING AND TYPE IN VOLTS | 250.0 AC |
CWJK | CASE MATERIAL | PLASTIC |
FREQ | FREQUENCY IN HERTZ | 400.0 ALL LOCATIONS |
THSD | THREAD SERIES DESIGNATOR | UNC |
TTQY | TERMINAL TYPE AND QUANTITY | 6 THREADED STUD |
Relevant Components for NSN - 5925-00-173-1036, 5925001731036 | ||||
5998-01-263-4512 (5998012634512) | 5935-01-068-1639 (5935010681639) | 5985-01-024-0423 (5985010240423) | 5940-01-665-1586 (5940016651586) | |
5962-01-423-8361 (5962014238361) | 5905-00-856-6684 (5905008566684) | 5905-00-106-1414 (5905001061414) | 5995-01-682-7226 (5995016827226) | |
5995-01-196-4177 (5995011964177) | 5945-00-239-8528 (5945002398528) | 5962-01-128-3294 (5962011283294) | 5965-01-661-2964 (5965016612964) | |
If You’re Ever Looking for NSN parts Or Have an Aircraft On Ground Situation, Don’t forget That We offer Competitive Pricing and Guaranteed On-Time Delivery.